Henley Power’s 2 MWh containerised BESS serves IPP solar farms, wind balancing projects, utility substations, and grid-forming sites at the 2 MWh scale across European deployments. The HLY-BESS-Utility-2MWh delivers 2,232 kWh in a single 20-ft ISO container with liquid-cooled LFP and a 1,331 Vdc architecture. Manufactured in Dezhou, Shandong. European projects serviced from Romania across a 9-region service network.
| Battery System | ||
| Chemistry | LiFePO₄ (LFP) — Cobalt-Free · EU Reg 2023/1542 | LiFePO₄ (LFP) — Cobalt-Free · EU Reg 2023/1542 |
| Cell Specification | 3.2 V / 314 Ah prismatic | 3.2 V / 314 Ah prismatic |
| Cell Sourcing | Tier-1 LFP cells from publicly listed manufacturers, multi-supplier homologated. Specific supplier identification shared on request after NDA. | Tier-1 LFP cells from publicly listed manufacturers, multi-supplier homologated. Specific supplier identification shared on request after NDA. |
| Battery Configuration | 166 V / 1P52S per rack | 332.8 V / 1P104S per rack |
| Number of Clusters | 4 clusters | 8 clusters |
| Rated Energy Capacity | 1,045 kWh | 2,232 kWh |
| System Voltage Range (DC) | 650–949 Vdc · 832 Vdc nominal | 1,123–1,497 Vdc · 1,331 Vdc nominal |
| Charge / Discharge Rate | 0.2C to 0.5C standard · 1C custom configuration available per project | 0.2C to 0.5C standard · 1C custom configuration available per project |
| Cycle Life | ≥10,000 cycles @ 80% DoD · EOL ≥70% SOH · per IEC 62620, ambient 25 °C · cell-level data under NDA | ≥10,000 cycles @ 80% DoD · EOL ≥70% SOH · per IEC 62620, ambient 25 °C · cell-level data under NDA |
| Round-Trip Efficiency | ≥94% AC-AC at 0.5C, 25 °C ambient, beginning of life | ≥94% AC-AC at 0.5C, 25 °C ambient, beginning of life |
| Design Life | 25 years | 25 years |
| Warranty | 5 years system · 5 years optional extension (battery) | 5 years system · 5 years optional extension (battery) |
| Thermal Management & Environment | ||
| Cooling Method | Intelligent liquid cooling · Cell ΔT < 2.5 °C | Intelligent liquid cooling · Cell ΔT < 2.5 °C |
| Operating Temperature | −40 °C to +60 °C | −40 °C to +60 °C |
| Maximum Operating Altitude | 4,000 m (derated above 2,000 m) | 4,000 m (derated above 2,000 m) |
| Noise Level | ≤75 dB(A) at 1 m | ≤75 dB(A) at 1 m |
| Enclosure & Protection | ||
| Container Type | 20 ft Standard ISO · Outdoor · Plug-and-Play | 20 ft Standard ISO · Outdoor · Plug-and-Play |
| Dimensions (L × W × H) | 5,274 × 2,893 × 2,896 mm | 6,058 × 2,438 × 2,896 mm |
| Weight | ~15 T | ~34 T |
| IP Rating | IP54 (container) · IP66 (battery module) | IP54 (container) · IP66 (battery module) |
| Anticorrosion Grade | C4 standard · C5 optional (coastal & marine) | C4 standard · C5 optional (coastal & marine) |
| Safety & Fire Protection | ||
| Fire Detection | Pack-level thermal runaway · Multi-level BMS | Pack-level thermal runaway · Multi-level BMS |
| Fire Suppression | Aerosol (standard) · Water suppression (optional) | Aerosol (standard) · Water suppression (optional) |
| Explosion Protection | 3-level design · Pressure relief vents | 3-level design · Pressure relief vents |
| System Availability | ≥99% annual uptime | ≥99% annual uptime |
| PCS Response Time | ≤20 ms (primary frequency regulation) | ≤20 ms (primary frequency regulation) |
| Communication & Control | ||
| Communication Protocols | Modbus TCP · Modbus RTU · CAN · IEC 60870-5-104 · IEC 61850-7-420 (DER) and IEC 61850-8-1 (substation) optional | Modbus TCP · Modbus RTU · CAN · IEC 60870-5-104 · IEC 61850-7-420 (DER) and IEC 61850-8-1 (substation) optional |
| Communication Interfaces | CAN / RJ45 / RS485 | CAN / RJ45 / RS485 |
| EMS Platform | Cloud EMS · AI dispatch · OTA upgrade · Remote O&M | Cloud EMS · AI dispatch · OTA upgrade · Remote O&M |
| Service | ||
| Service Centres | 9-region active and expansion service network · spare parts stocked in-region for primary markets | 9-region active and expansion service network · spare parts stocked in-region for primary markets |
| Response SLA | 1-hour diagnostic response · 24-hour solution path including on-site dispatch where required | 1-hour diagnostic response · 24-hour solution path including on-site dispatch where required |
This system uses LiFePO₄ chemistry aligned with EU Battery Regulation supply chain due diligence and carbon footprint declaration requirements. CE marked. Digital Battery Passport readiness tracks the 18 February 2027 mandate — we’re already mapping declarations at cell and module level. EU-jurisdiction warranty service from Romania, with spare parts stocked in-region.